Installation and Commissioning

Coolcentric Professional Services (CPS) provides expert installation and commissioning services for all LiquiCool® equipment as well as ancillary items required to complete the installation and ensure your equipment's proper operation. CPS installation, commissioning, re-commissioning and combined service offerings are performed by Coolcentric service technicians.

Installation service may include but is not limited to the following:

Installation and Commissioning
  • Affix LiquiCool Rear Door Heat Exchanger unit(s) to compatible racks per the site schedule
  • Attach quick-coupling hose assemblies to Rear Door Heat Exchanger unit(s)
  • Attach quick-coupling hose assemblies to LiquiCool Coolant Distribution Unit(s) (CDU) or custom manifolds at supply ends
  • Secure hose assemblies to stringer, hanger or floor as specified in site schedule
  • Sub-contract installation and attachment of chilled water feeders to CDU unit(s)
  • Sub-contract electrical installation of CDU unit(s) to building power system

Commissioning services may include but are not limited to the following:

  • Check the state and operation of Rear Door Heat Exchanger units
  • Fill CDU unit(s) reservoir with treated water
  • Release air from any bleed points as needed
  • Check the condition of the system fluid
  • Add new, treated make-up fluid to the system to accommodate for installation losses
  • Log the operational characteristics of the CDU unit(s) for predictive maintenance
  • Retrieve and store log and alarm data from any CDU unit(s)
  • Upgrade firmware if needed or requested (Clients are given prior notice)
  • Perform any engineering change orders (ECO) on equipment as needed
  • Conduct performance tests on equipment using 'load' equipment if requested
  • Balancing of fluid flow per rack